Power Quality Solutions for Renewable Energy & Storage

CHITEK controls harmonic interleaving, flicker and reactive swing at PV, wind and battery-storage interconnect points using combined SVG and AHF equipment. Several inverters switching on one bus interleave their emissions, and charge-to-discharge transitions produce a reactive step. Compliance is assessed where the grid operator measures it: the point of common coupling.

PV inverters, full-power wind converters and battery PCS units all switch at high frequency. Several units on one interconnect point interleave their harmonics, and the charge and discharge transition produces a reactive step and a flicker event. The compliance question is what the grid operator measures at the point of common coupling.

Reviewed by the CHITEK power quality engineering team · Last updated

AHF or SVG at an interconnect point?

At a PV, wind or storage interconnect the two problems arrive together, because the same inverters produce both switching harmonics and reactive swing.

Aspect AHF (Active Harmonic Filter) SVG (Static Var Generator)
What it does Injects a compensating current that cancels the harmonic current drawn by non-linear loads. Supplies or absorbs reactive power continuously to hold power factor and support voltage.
Primary target Current distortion (THDi) and harmonic spectrum at the point of common coupling. Power factor, voltage fluctuation and reactive demand across the load cycle.
Typical trigger VFD banks, rectifiers, welding sets, induction furnaces, LED drivers, UPS rectifiers. Low or swinging power factor, voltage sag and rise, weak or long feeders, EV load steps.
Behaviour at light load Compensation scales with the measured harmonic current, so output falls as load falls. Holds output as required to reach the target power factor even at near-zero active load.
Use in this sector Harmonic correction where multi-inverter interleaving or LCL filter interaction pushes emission past the grid limit. Reactive support and voltage hold as irradiance or state of charge changes, and to avoid leading power factor at low output.

Compliance is assessed at the point of common coupling, so the survey should be taken there rather than at the inverter terminals.

Typical power quality problems

Solar PV Power Station

Utility-scale / Distributed / Agri-PV

Inverter Harmonics

Wideband oscillation from multi-inverter

>8%

THD

  • Resonance Risk — LCL filter + grid impedance resonance, wideband oscillation, inverter cascade trip
  • Grid Violation — Harmonic emission exceeds GB/T 14549 at PCC, grid company curtailment order

Grid Voltage

Fluctuation from irradiance variation

PF Low

Reactive Diff.

  • Dispatch Penalty — Reactive power deviation from dispatch setpoint, AVC assessment failure, revenue deduction
  • Voltage Limit — Cloud-edge effect, ±10% voltage swing in < 1min, reverse power protection trip

DC Ripple

AC side reflection from DC ripple

DC Bias

Xfmr Overheat

  • Core Saturation — DC component causes transformer core half-cycle saturation, magnetizing current surge, humming
  • Efficiency Loss — Excess core loss + harmonic copper loss, PR (performance ratio) drops 2-3 percentage points

Wind Power Farm

Onshore / Offshore / Distributed

Converter Harmonics

Low-order distortion from full-power converter

>10%

THD

  • Grid Rejection — 5th/7th harmonic dominant, utility interconnect test failure, energization delay cost
  • Collector Resonance — 35kV cable capacitance + transformer inductance, parallel resonance near 7th harmonic

Wind Fluctuation

Reactive surge from gust/turbulence

Reactive

Swing

  • PF Penalty — Rapid reactive swing from wind gusts, monthly PF < 0.85, utility reactive charge 2x
  • AVC Hunting — AVC system oscillation chasing wind variation, tap changer excessive wear, 5x maintenance

Box Transformer

Phase imbalance from auxiliary load

>5%

Unbalance

  • Limit Violation — Single-phase auxiliary supply imbalance, negative sequence exceeds grid code limit
  • Overheat Trip — Imbalance + harmonic combine, winding hot-spot temperature alarm, forced curtailment

Energy Storage System

Grid-side / User-side / Source-side

Charge/Discharge

Harmonic stack from multi-PCS

>6%

THD

  • Grid Pollution — Multi-PCS interleaving harmonics, PCC THD exceeds GB/T 34120, grid operator warning
  • Battery Ripple — AC ripple current on DC bus, lithium plating acceleration, cycle life reduced 20%

PCS Reactive

Lag regulation at low load

< 0.9

PF

  • Penalty Fee — Standby mode reactive consumption triggers penalty, monthly charge + demand ratchet
  • Regulation Fail — AGC/AVC joint dispatch setpoint not met, ancillary service qualification revoked

Grid Point

Voltage flicker at interconnect

> 0.8

Pst

  • Interconnect Fail — Flicker Pst > 0.8 during mode transition, grid interconnect agreement non-compliance
  • Islanding Risk — Grid disturbance detection confused by flicker, unintentional islanding, safety hazard

Renewable Energy case studies

Each case below is written up the same way: what the site was, what the survey measured before anything was specified, what was installed, and what the acceptance test showed afterwards. Projects marked Typical Configuration are illustrative — sizing for those always starts from a site survey rather than from the table.

Typical Configuration — Solar PV Plant

Typical Configuration · Solar PV

Typical Configuration — Solar PV Plant

Illustrative configuration — sizing starts from a site power-quality survey

Background

An illustrative arrangement for a utility-scale or distributed PV plant: SVG at the step-up bus, AHF on the inverter AC feeders.

Equipment installed

  • SVG
    SVG × 2 units Static Var Generator Step-up bus reactive support
  • AHF-200A
    AHF-200A × 4 units Active Harmonic Filter Inverter AC feeder harmonic filtering

Project overview

For utility-scale and distributed PV, the usual arrangement is an SVG at the step-up bus plus AHF on the inverter AC feeders. Multi-inverter resonance and cloud-edge reactive swings are the two failure modes — both need a measurement campaign before ratings are fixed.

Why there is no before / after here

Illustrative configuration — not a specific delivered project. Reference projects in this sector are available on request.

Key results

  • Resonance scan across the collector network before sizing
  • Reactive envelope checked against the AVC dispatch setpoint
  • Ask us for reference projects in solar PV

Frequently asked questions

What power quality problems appear at a PV or storage interconnect point?

Wideband harmonic emissions from many inverters switching together, reactive swing as irradiance or state of charge changes, and voltage flicker at the interconnect. Multi-inverter LCL filter interaction can also produce resonance.

Why does power factor drop at low output?

Inverters and PCS units are rated for active power. At low output their reactive capability is a smaller share of what the plant needs, and cable and transformer capacitance can push the measured power factor leading or lagging depending on the hour.

Can one device handle both harmonics and reactive power?

A combined SVG plus AHF arrangement is the usual answer. The SVG holds power factor and voltage, the AHF removes switching harmonics, and the ratings are split according to what the survey finds.

What does grid compliance depend on?

The grid agreement and the local standard, measured at the point of common coupling. Emission limits, flicker and reactive capability are all assessed there, so the survey should be taken at that point rather than at the inverter terminals.

Related products

Solutions for other industries

Get a power quality assessment for your site

Every project on this page started with a measured survey. Send us your single-line diagram and load list and we will tell you what we would measure first.

Contact our engineers